Bit 9:  Inching 2 OFF command (L "Inching 2 OFF") 
The command is executed with an L signal. 
After the command has been accepted: 
♦  An OFF 1 command is automatically executed (description, refer to control word bit 0). 
Bit 10:  Control from the PLC command (H "Control from the PLC") 
The command is executed with an H signal  
Process data PZD (control word, setpoints) originating from a PLC
 which were sent via the SST1 interface of 
CU1, the CB/TB interface (option) and the SST/SCB interface (option),  are only evaluated if the command was 
accepted.  
♦  If several interfaces are operational, only the process data of the interfaces are evaluated, which transmit the 
H signal. 
♦  For an L signal, the last values are retained in the appropriate dual port RAM of the interface. 
An H signal appears in the visualization parameter r550 "control word 1", if one
 of the interfaces transmits an H 
signal! 
Bit 11:  Ud reduction command (H "Ud reduction requested") 
(See also Chapter 4.3.10.2) 
The command is executed with an H signal. 
After the command has been accepted: 
♦  The DC link voltage setpoint drops to the value set with P318:  
 
%00.100
318P
U35.1intSetpo
**
rectifier,Supply
=  
If the value of P330 is even, Ud setpoint lowering takes place abruptly. If it is odd, the setpoint is ramped 
down according to the discharge time in P330. 
♦  At the same time, the intermediate DC link voltage threshold for enabling the regenerating bridge is reduced 
to the following value if an autotransformer is not present (i.e. when 
17.1
U
U
rectifier,Supply
ngregenerati,Supply
< ): 
 
%00.100
318P
U35.1
**
ngregenerati,Supply
 
  This causes the signal "Regenerating ready"  (status word 1, bit 10) to switch to low. 
♦  The DC link should now discharge. 
♦  When the DC link voltage drops below the following threshold value 
 
071P35.1
%100
%2
%00.100
318P
U35.1
****
rectifier,Supply
+
 
  the message "Ud reduced" (status word 1, bit 13) is issued, and a converter connected to the DC link can 
regenerate. At the same time as the message "Ud reduced" is issued, for which the hysteresis of P319 
applies, the regenerating bridge is enabled such that the DC link voltage threshold for the message 
"Regenerating ready" is set to a higher value.  
 
♦  The appearance of a trailing edge of the Ud reduction command causes the output of the ramp-up/return 
element (precharging time P329) to be set to the current value of DC link voltage so that the DC link voltage 
setpoint can ramp up again from this value. 
 
♦  The L signal
 of the Ud reduction command causes the "Ud reduced" message (status word 1, bit 13) to be 
held low (regardless of the DC link voltage level) 