09.02  Start-Up 
Siemens AG    6SE7087-6AK85-1AA0 
4-59 
Rectifier/Regenerating Unit    Operating Instructions 
Index  Meaning for CBP2 
010 
L byte: Mirroring of P918 (CB bus addr.) 
H byte: Reserved 
011 
L byte: "Re-config. by CUD" counter 
H byte: "Initialization runs" counter 
012 
L byte: Error ID DPS manager error 
H byte: Reserved 
013 
L byte: PPO type found 
H byte: Reserved 
014 
L byte: Mirroring of "DWord specifier ref" 
015 
H byte: Mirroring of "DWord specifier act" 
016 
L byte: DPV1:DS_Write, pos. ack. counter 
H byte: Reserved 
017 
L byte: DPV1:DS_Write, neg. ack. counter 
H byte: Reserved 
018 
L byte: DPV1:DS_Read, pos. ack. counter 
H byte: Reserved 
019 
L byte: DPV1:DS_Read, neg. ack. counter 
H byte: Reserved 
020 
L byte: DP/T:GET DB99 pos. ack. counter 
H byte: DP/T:PUT DB99 pos. ack. counter 
021 
L byte: DP/T:GET DB100 ps. ack. counter 
H byte: DP/T:PUT DB100 ps. ack. counter 
022 
L byte: DP/T:GET DB101 ps. ack. counter 
H byte: DP/T:PUT DB101 ps. ack. counter 
023 
L byte: DP/T service neg. acknow. counter 
H byte: DP/T:Application association pos. acknow. counter 
024 
Reserved 
025 
Date of creation: Day, month 
026  Date of creation: Year 
027  Software version (Vx.yz, display x) 
028  Software version (Vx.yz, display yz) 
029  Software version: Flash-EPROM checks. 
030 Reserved 
031 Reserved 
032 Reserved 
 
Fault and alarm messages: 
For details about fault messages, see Section 7. 
Fault F080 
An error occurred as board CBP2 was being initialized, e.g. incorrect value of a CB parameter, incorrect 
bus address or defective module. 
Fault F081 
The heartbeat counter (counter on CBP2) which is monitored by SIMOVERT 6SE70 for "signs of life" 
from the board has not changed for at least 800 ms. 
Fault F082 
Failure of PZD telegrams or a fault in the transmission channel. 
 