Fault and Alarm Messages  09.02 
7-10  Siemens AG    6SE7087-6AK85-1AA0 
  Rectifier/Regenerating Unit    Operating Instructions 
Alarm 
No. 
Parameter 
No. 
⎯⎯ 
Bit No. 
Description  Countermeasures 
A049 
P956 
⎯⎯ 
0 
no Slave 
In the case of serial I/O (SCB1 with SCI1/2), no 
slave is connected and/or the fiber optic conductor 
is interrupted or the slaves have no voltage.
 
P660 SCI AnalogInConf
 
Check the slave. 
Check the cable. 
A050 
P956 
⎯⎯ 
1 
Slave not ok 
In the case of serial I/O, the slaves required 
according to the parameter settings are not 
available (slave number an/or slave type).
 
Check P660 SCI AnalogInConf 
A051 
P956 
⎯⎯ 
2 
Peer Bdrate 
In a peer-to-peer connection, the baud rate 
selected is too high and/pr different
 
Match the baud rates of the SCB modules connected to 
each (
P684 SST/SCB Baudrate) 
A052 
P956 
⎯⎯ 
3 
Peer PrD-L 
In a peer-to-peer connection, an excessive process 
data length has been set (>5).
 
Reduce the number of words 
P686 SCom/SCB # PrDat. 
A053 
P956 
⎯⎯ 
4 
Peer Lng f.
 
In a peer-to-peer connection, the process data 
length of the sender and receiver do not agree
 
 
Match the word lengths of the sender and receiver
 
P686 SCom/SCB # PrDat
 
A065 
P957 
⎯⎯ 
0 
Auto Restart 
The line voltage is outside the tolerance band at 
the moment (e.g. power outage). The firing pulses 
are therefore inhibited. On power recovery, 
however, the WEA option (P366) implements an 
auto restart. 
Important  
An auto restart may constitute a danger for persons and 
property. Make sure you really want to have auto restart 
(WEA). 
If necessary, change
 P366 WEA. 
A081.. 
A096 
r958 
⎯⎯ 
0...15 
CB Warning 1...16 
See user's manual for the CB module 
 
A097.. 
A112 
r959 
⎯⎯ 
0...15 
TB Warning 1   16
 
See user's manual for the TB module
 
 
A113.. 
A128 
r960 
⎯⎯ 
0...15 
TB Warning 17...32
 
See user's manual for the TB module
 
 
 