EasyManua.ls Logo

Siemens 7SR105 Rho - Measurands

Siemens 7SR105 Rho
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 - 7SR105 Rho · Data Communications Definitions
© 2018 Siemens Protection Devices Chapter 4 - Page 19 of 70
FUN INF Description ASDU COT
20 Ack, Nak
1 SE, GI
200 157 User SP Command 8
20 Ack, Nak
1 SE, GI
200 158 User DP Command 1
20 Ack, Nak
1 SE, GI
200 159 User DP Command 2
20 Ack, Nak
1 SE, GI
200 160 User DP Command 3
20 Ack, Nak
1 SE, GI
200 161 User DP Command 4
20 Ack, Nak
1 SE, GI
200 162 User DP Command 5
20 Ack, Nak
1 SE, GI
200 163 User DP Command 6
20 Ack, Nak
1 SE, GI
200 164 User DP Command 7
20 Ack, Nak
1 SE, GI
200 165 User DP Command 8
20 Ack, Nak
200 255 Blocked By Interlocking 1 SE, GI
255 0 General Interrogation (GI) Initiation 7 Init. GI
255 0 General Interrogation (GI) End 8 End of GI
255 0 Time Synchronisation 6
Time
Synch.
3.4.2 Measurands
The following Measurand EVT and INF numbers apply to this device.
FUN INF Description ASDU COT
183 148
Measurand I
L1,2,3,
---
I
L1
(2.4x) (Window 1%)
I
L2
(2.4x) (Window 1%)
I
L3
(2.4x) (Window 1%)
9
Cyclic -
Refresh
rate 5
seconds
or value
change
greater
than
Window x
%.
185 132
Temperature T
1, 2, 3, 4, 5, 6
---
T
1
(1.2x) (Window 0.4%)
T
2
(1.2x) (Window 0.4%)
T
3
(1.2x) (Window 0.4%)
T
4
(1.2x) (Window 0.4%)
T
5
(1.2x) (Window 0.4%)
T
6
(1.2x) (Window 0.4%)
9
Cyclic -
Refresh
rate 5
seconds
or value
change
greater
than
Window x
%.

Table of Contents