EasyManua.ls Logo

Siemens 7SR105 Rho - Circuit-Breaker Fail (50 BF)

Siemens 7SR105 Rho
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR105 Rho and 7SR17 Rho Applications Guide
©2018 Siemens Protection Devices Chapter 7 Page 27 of 31
4.7 Circuit-Breaker Fail (50BF)
Where a circuit breaker fails to operate to clear fault current the power system will remain in a hazardous state
until the fault is cleared by remote or back-up protections. To minimise any delay, CB Failure protection provides
a signal to either re-trip the local CB or back-trip ‘adjacent’ CBs.
The function is initiated by the operation of user selectable protection functions or from a binary input.
The relay incorporates a two-stage circuit breaker fail feature. For some systems, only the first will be used and
the CB Failure output will be used to back-trip the adjacent CB(s) e.g. the busbar incomer. On other systems,
however, this output will be used to re-trip the local CB to minimise potential disruption to the system; if possible
via a secondary trip coil and wiring. The second CB Failure stage will then be used to back-trip the adjacent
CB(s).
50
BF
BACK-TRIP
50BF-2 Delay
M
RE-TRIP
50BF-1 Delay
S/Stn Busbar
Figure 4.7 Circuit Breaker Fail
50BF Setting
The current setting must be set below the minimum protection setting current.
50BF-1 Delay/50BF-2 Delay
The time delay setting applied to the CB Fail protection must be in excess of the longest CB operate time + relay
reset time + a safety margin.
Stage 1 (Retrip)
Trip Relay operate time 10 ms
7SR105 or 7SR17 Disengaging Time 50 ms
CB Trip time 80 ms
Safety Margin 60 ms
50BF-1 Delay 200 ms
Stage 2 (Back Trip)
First BF Time Delay 200 ms
Trip Relay operate time 10 ms
7SR105 or 7SR17 Disengaging Time 50 ms
CB Trip time 80 ms
Margin 60 ms
50BF-2 Delay 400 ms

Table of Contents

Related product manuals