7SR105 Rho Technical Manual
Chapter 4 - Page 50 of 70 © 2018 Siemens Protection Devices
Binary Output Status Points
Static (Steady-State) Object Number: 10
Change Event Object Number: 11
Control Relay Output Blocks (CROB) Object Number: 12
Binary Output Command Event Object Number: 13
Static Variation reported when variation 0 requested: 1 (Binary Output w/o status)
or 2 (Binary Output with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time)
or 2 (Binary Output Event with Time)
Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time)
or 2 (Command Status with Time)
Point
Index
Description
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 10
Default
Variation
Event
Object 11
Default
Command
Event
Object 13
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Command
Event
Object 13
CROB
Supported
Operations
Default
CROB
Operations
Latch On
Paired
Close
33
LED reset, write only
location.
0 2 2 0 1
Pulse On
Latch On
Paired
Close
Pulse On
34 Settings Group 1 0 2 2 0 1
Pulse On
Latch On
Paired
Close
Latch On
35 Settings Group 2 0 2 2 0 1
Pulse On
Latch On
Paired
Close
Latch On
44 E/F off/on 0 2 2 0 1
Pulse On
Pulse Off
Latch On
Latch Off
Paired
Close
Paired
Trip
Pulse On
Pulse Off
Latch On
Latch Off
48
Reset CB Total Trip
Count, write only location.
0 2 2 0 1
Pulse On
Latch On
Paired
Close
Pulse On
49
Reset CB Delta Trip
Count, write only location.
0 2 2 0 1
Pulse On
Latch On
Paired
Close
Pulse On
53 Reset I^2t CB Wear 0 2 2 0 1
Pulse On
Latch On
Paired
Close
Pulse On
54 CB 1 0 2 2 0 1
Pulse On
Pulse Off
Latch On
Latch Off
Paired
Close
Paired
Trip
Pulse On
Pulse Off
Latch On
Latch Off
59
Demand metering reset,
write only location.
0 2 2 0 1
Pulse On
Latch On
Paired
Close
Pulse On
88 Remote mode 0 2 2 0 1 Pulse On Pulse On