Chapter 4 - 7SR105 Rho · Data Communications Definitions
© 2018 Siemens Protection Devices Chapter 4 - Page 53 of 70
Binary Output Status Points
Static (Steady-State) Object Number: 10
Change Event Object Number: 11
Control Relay Output Blocks (CROB) Object Number: 12
Binary Output Command Event Object Number: 13
Static Variation reported when variation 0 requested: 1 (Binary Output w/o status)
or 2 (Binary Output with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time)
or 2 (Binary Output Event with Time)
Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time)
or 2 (Command Status with Time)
Point
Index
Description
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 10
Default
Variation
Event
Object 11
Default
Command
Event
Object 13
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Command
Event
Object 13
CROB
Supported
Operations
Default
CROB
Operations
Latch Off
Paired
Close
Paired
Trip
113 User DP Command 7. 0 2 2 0 1
Pulse On
Pulse Off
Latch On
Latch Off
Paired
Close
Paired
Trip
Pulse On
Pulse Off
114 User DP Command 8. 0 2 2 0 1
Pulse On
Pulse Off
Latch On
Latch Off
Paired
Close
Paired
Trip
Pulse On
Pulse Off
117
Reset Thermal Capacity,
write only location.
0 2 2 0 1
Pulse On
Latch On
Paired
Close
Pulse On
118
Reset 66 Motor Starts,
write only location.
0 2 2 0 1
Pulse On
Latch On
Paired
Close
Pulse On
119
Reset Total Motor Starts,
write only location.
0 2 2 0 1
Pulse On
Latch On
Paired
Close
Pulse On
120
Reset Motor Run Time,
write only location.
0 2 2 0 1
Pulse On
Latch On
Paired
Close
Pulse On
121
Reset Motor Total Run
Time, write only location.
0 2 2 0 1
Pulse On
Latch On
Paired
Close
Pulse On
122
Reset Motor Last Start
Info, write only location.
0 2 2 0 1
Pulse On
Latch On
Paired
Close
Pulse On
123
Reset Motor Stop Time,
write only location.
0 2 2 0 1
Pulse On
Latch On
Pulse On