EasyManua.ls Logo

Siemens 7SR105 Rho - Page 189

Siemens 7SR105 Rho
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR105 Rho and 7SR17 Rho Applications Guide
©2018 Siemens Protection Devices Chapter 7 Page 16 of 31
values indicates the magnitude of thermal capacity used to start. This amount must always be available before a
restart is permitted. For safety, this figure should be multiplied by 1.25. For example, if 20% of capacity is used
during starting, then 20% x 1.25 = 25%, and the Thermal Restart Inhibit setting should be 75%.
Alternatively auto-setting can be selected.
Thermal Restart Mode
The default setting ‘Capacity’ can be used.
Summary of Thermal Settings
0.10
1.00
10.0
0
100.0
0
1000.0
0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
Overload Level (Multiple of Setting Itheta)
Time (secs)
4.8 x Itheta
0.95 x Iθ
2 x run up = 8 secs
TauH =
4 mins
Figure 2.2-2 Summary of Thermal Settings
Thermal overload (Itheta) = 0.9 x In
Heating Constant TauH = 4 minutes
Starting Constant TauS = 1
Cooling Constant TauC = 10
H/C = 64%
49 Capacity Alarm Setting = 95%
Load Alarm Setting = 1.0 x Itheta
Stall Protection
The fundamentals of this protection feature are explained in section 2.1.2.
In the example being considered the run-up time is 4 seconds and the safe stall time is 11 seconds. In this case
the thermal characteristic gives sufficient protection for normal starting and a stalled motor condition can be
detected by current/time grading. The ’14-1 Delay’ setting should be set to be longer than the run-up time and
less than the safe stall time, a time setting of 5 seconds should be chosen.
If the motor starting time is equal to or exceeds the stall withstand time it is necessary to use a stall element that
can operate only when the motor is running, by either:-
Selecting Gn14-2 Control to ‘Running’, or
Using a tachometric switch mounted on the rotor to signal that the motor is running. A relay binary input
is configured to be energised by this switch and is programmed to the ‘No Accel.’ function in the input
configuration menu. Select Gn14-2 Control to ‘No Accel.

Table of Contents

Related product manuals