EasyManua.ls Logo

Siemens 7SR105 Rho - Page 82

Siemens 7SR105 Rho
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR105 Rho Performance Specification
© 2018 Siemens Protection Devices Chapter 3 Page 6 of 17
Table 1-9 Temperature Inputs
Number 6
Measuring Range -50 ºC to +250 ºC
100 % Tset, ± 2 % or ± 2 ºC,
For Cu10: ± 2 % or ± 5 ºC
Response time < 3 s
Sensing current < 0.5 mA
Table 1-10 Rear Communication Port
Quantity 1 No.
Electrical connection RS485, 2 wire electrical
Protocol Support MODBUS RTU,
IEC 60870-5-103,
DNP 3.0
Rate
Data Transfer rate:
2400 bps to 38400 bps
Table 1-11 Front Communication Port
Quantity 1 No.
Electrical connection USB, Type B
Table 1-12 Data Storage
Fault Record 15
Waveform Record 15 Rec x 1 s
7 Rec x 2 s
3 Rec x 5 s
1 Rec x 15 s
Pre trigger 10…90 %
Events 1000 events (1 ms resolution)

Table of Contents