EasyManua.ls Logo

Siemens 7SR105 Rho - Page 87

Siemens 7SR105 Rho
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR105 Rho Performance Specification
© 2018 Siemens Protection Devices Chapter 3 Page 11 of 17
Insulation Resistance
IEC/EN 60255-27: Edition 2:
2013-10
Test voltage: 500 V DC
> 100 M ohm
Test duration: > 5 s
Protective Bonding
Resistance
IEC/EN 60255-27: Edition 2:
2013-10
Test voltage: < 12 V
AC/DC
< 0.1 Ohm
Test duration: 1 min
Bonding resistance
Protective Bonding
Continuity
IEC/EN 60255-27: Edition 2:
2013-10
Accessible conductive
parts should be bonded
with the protective
conductor terminal
Low current
continuity test
Flammability of
Insulating Materials,
Components and Fire
enclosures
IEC/EN 60255-27: Edition 2:
2013-10
Structure Part
Standard for
insulating material
of flammability
class
Terminals Class UL 94 V-0
Terminal Mounting Class UL 94 V-0
Wiring (CT) (N)2GFAF (VDE)
Components mounting Class UL 94 V-0
Enclosure Class UL 94 V-0
PCB Class UL 94 V-0
LCD Class UL 94 V-0
Single Fault Condition
IEC/EN 60255-27: Edition 2:
2013-10
Assessment of:
Insulation between
circuits and parts
Compliance with
requirements for
protection against the
spread of fire
Overloads
Intermittently rated
resistors
Compliance with
requirements for
mechanical protection
The equipment
shall not present
a risk of electric
shock or fire after
a single-fault test.
Marking and
Documentation
IEC 61010-1: 2010 Clause No. 5 -
Protection against
electric shock
Clause No. 6
-
Protection against
mechanical hazard
Clause No. 7
-

Table of Contents