7SR224 Argus Commissioning & Maintenance Guide
The copyright and other intellectual property rights in this document, and in any model or article produced from it
(and including any registered or unregistered design rights) are the property of Siemens Protection Devices
Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval
system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be
reproduced from this document unless Siemens Protection Devices Limited consent.
While the information and guidance given in this document is believed to be correct, no liability shall be accepted
for any loss or damage caused by any error or omission, whether such error or omission is the result of
negligence or any other cause. Any and all such liability is disclaimed.
©2010 Siemens Protection Devices Limited
7SR224 Recloser Controller
Overcurrent Relay
Document Release History
This document is issue 2010/05. The list of revisions up to and including this issue is:
2008/03 First issue
2008/06 Second issue
2009/09 Third issue
2010/04 Fourth issue
2010/05 Fifth issue. Document reformatted due to rebrand.
Software Revision History
2008/03 2435H80011R2d-1a First Release
2008/06 2435H80011R3d-2b Second Release. Loss Of Voltage
2008/10 2435H80011R4-3 Third Release. Single/Triple AutoReclose function
2009/09 2435H80011R4c-3b Fourth Release. Software maintenance release.
2010/04 2434H80011R4d-4 Fifth Release. Synchronising

Table of Contents

Other manuals for Siemens 7SR224

Questions and Answers

  • C
    Charles MitchellSep 8, 2025
    What to do if Siemens 7SR224 Controller status inputs do not work?
    • T
      timothy40Sep 9, 2025
      If the status inputs on your Siemens Controller aren't working, ensure the correct DC voltage is applied with the correct polarity. Also, check that the status input settings, such as the pick-up and drop-off timers and the status inversion function, are set correctly.
  • M
    Matthew PetersonAug 23, 2025
    How to troubleshoot communication issues with a Siemens 7SR224 Controller?
    • J
      Jonathon MataAug 23, 2025
      If you cannot communicate with the Siemens Controller, verify that all communication settings match those used by ReyDisp Evolution. Also, ensure the Tx and Rx fibre-optic cables are connected correctly (Tx –> Rx and Rx –> Tx). Check that all cables, modems, and fibre-optic cables are functioning correctly and that IEC 60870-5-103 is specified for the connected port (COM1, COM2, COM3, or COM4).
  • C
    Cynthia MasseyAug 25, 2025
    Why Siemens 7SR224 relays will not communicate in a ring network?
    • J
      Jessica TorresAug 26, 2025
      If the Siemens Controller relays will not communicate in a ring network, check the following: * Ensure that the Data Echo setting on all relays is set to ON. * Verify that all relays are powered up. * Confirm that all relays have unique addresses.
  • A
    andersonsuzanneAug 27, 2025
    What to do if status inputs do not work on a Siemens Controller?
    • D
      Daisy YangAug 27, 2025
      If the status inputs on your Siemens Controller are not working, check that the correct DC voltage is applied with the correct polarity. Also, verify that the status input settings, like the pick-up and drop-off timers and the status inversion function, are correctly configured.
  • G
    garrettericAug 28, 2025
    How to fix a Siemens 7SR224 when the backlight is on but no text is visible?
    • C
      Claudia WheelerAug 28, 2025
      If the backlight is on but no text can be seen on your Siemens Controller, try adjusting the contrast.
  • G
    Glenn RussellSep 22, 2025
    What to do if the LCD screen flashes continuously on Siemens 7SR224 Controller?
    • E
      Erin FranklinSep 22, 2025
      If the LCD screen on your Siemens Controller flashes continuously, this indicates a general failure. Contact a Siemens Protection Devices Ltd. representative.
  • C
    Chelsey MartinSep 16, 2025
    Why does Siemens 7SR224 Controller display instruments without user input?
    • R
      Ronald RiddleSep 16, 2025
      If your Siemens Controller displays one instrument after another without user intervention, this is normal operation, as default instruments are enabled. To customize this, remove all instruments from the default list and add only those that are required.
  • P
    Perry RodriguezSep 18, 2025
    What does it mean when the Protection Healthy LED flashes on Siemens 7SR224 Controller?
    • M
      Michael CohenSep 18, 2025
      If the Protection Healthy LED flashes on your Siemens Controller, this indicates a general failure. Contact a Siemens Protection Devices Ltd. representative.
  • J
    Jasmine NavarroSep 7, 2025
    Why Siemens Controllers will not communicate in a ring network?
    • L
      Luis ReedSep 7, 2025
      If Siemens Controllers won't communicate in a ring network, check that the Data Echo setting on all relays is set to ON. Ensure that all relays are powered up and have unique addresses.
  • A
    Amanda KellySep 4, 2025
    What to do if my Siemens 7SR224 won’t accept the password?
    • A
      Ariana RiceSep 4, 2025
      If your Siemens Controller isn't accepting the password, ensure you're entering the correct password. If you've forgotten the correct password, note the Numeric Code displayed on the Change Password screen (e.g., Change password = 1234567) and communicate this code to a Siemens Protection Devices Ltd. representative to retrieve the password.

Summary

Document Release History

Software Revision History

Details revisions and versions of the document software.

Section 1: Common Functions

1.1 Overview

Provides a general introduction to the common functions of the relay.

1.2 Pre-testing Procedures

Covers essential steps before conducting relay tests, including safety and equipment.

Section 2: Protection Functions

2.1 Phase Directional Polarity Check

Procedure for verifying the directional polarity of phase overcurrent elements.

2.2 Phase Overcurrent (67;50,67;51)

Testing procedures for phase overcurrent protection elements.

2.3 Voltage Controlled Overcurrent (51 V)

Details testing for the voltage-controlled overcurrent protection function.

2.11 Thermal Overload (49)

Testing procedures for the thermal overload protection function.

2.12 Over;Under Voltage (27;59)

Covers testing for various over and under voltage protection functions.

Section 3: Supervision Functions

3.1 CB Fail (50 BF)

Testing procedure for the Circuit Breaker Fail supervision function.

3.2 Voltage Transformer Supervision (60 VTS)

Procedures for testing voltage transformer supervision functionality.

3.4 Current Transformer Supervision (60 CTS)

Testing procedures for current transformer supervision functionality.

3.5 Broken Conductor (46 BC)

Testing methodology for the broken conductor detection function.

Section 4: Control & Logic Functions

4.1 Autoreclose (79)

Details testing procedures for the autoreclose control function.

4.2 Synchronising

Covers testing of the synchronising logic for recloser control.

Section 5: Testing and Maintenance

5.1 Periodic Tests

Outlines recommended periodic tests for relay maintenance.

5.3 Troubleshooting

Provides guidance for diagnosing and resolving relay issues.

Section 6: Relay Software Upgrade Instructions

6.1 General & Identify Software

Covers general upgrade guidelines and identifying current software versions.

6.2 Software Information & Configuration

Details software information and product configuration data.

6.3 Firmware Loading Procedures

Explains procedures for loading firmware, including USB port usage.

6.3.1 Solving Software Upload Problems

Solutions for common issues encountered during software uploads.

Siemens 7SR224 Specifications

General IconGeneral
Rated Current1A or 5A
Frequency50 / 60 Hz
Rated Frequency50 / 60 Hz
Number of Overcurrent Stages3
Number of Earth Fault Stages1
Current Input1A or 5A
Communication ProtocolsModbus RTU
Operating Temperature Range-25°C to +55°C
Protection FunctionsOvercurrent, Earth Fault
Auxiliary Supply Voltage24-250V DC/48-265V AC