7SR224 Argus Commissioning & Maintenance Guide
©2010 Siemens Protection Devices Limited Chapter 6 Page 12 of 73
1.7 Relay Case Shorting Contacts
CT inputs and terminals B25-B26 (Relay Withdrawn Alarm) are fitted with case mounted shorting contacts which
provide a closed contact when the relay is withdrawn from the case. The operation of these contacts should be
checked.
CT Shorting contacts checked
Relay Withdrawn Alarm Checked