EasyManua.ls Logo

Siemens 7SR242 - Section 5: Supervision Functions; Circuit Breaker Failure Protection

Siemens 7SR242
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR242 Duobias Description Of Operation
©2010 Siemens Protection Devices Limited Chapter 1 Page 44 of 52
Section 5: Supervision Functions
5.1 Circuit Breaker Failure (50BF)
Two CB Fail elements are provided – one element per winding.
Each circuit breaker fail function has two time delayed outputs that can be used for combinations of re-tripping or
back-tripping. CB Fail outputs are given after elapse of the 50BF-n-1 Delay or 50BF-n-2 Delay settings. The two
timers run concurrently.
The circuit breaker fail protection time delays are initiated either from:
An output Trip Contact of the relay (MENU: OUTPUT CONFIG\BINARY OUTPUT CONFIG\CBn Trip
Contacts), or
A binary or virtual input assigned to 50BF-n Ext Trip (MENU: INPUT CONFIG\INPUT MATRIX\50BF Ext
Trip).
A binary or virtual input assigned to 50BF-n Mech Trip (MENU: INPUT CONFIG\INPUT MATRIX\ 50BF-
n Mech Trip).
CB Fail outputs will be issued providing any of the 3 phase currents are above the 50BF-n Setting or the current
in the fourth CT is above 50BF-n-I4 for longer than the 50BF-n-n Delay setting, or for a mechanical protection trip
the circuit breaker is still closed when the 50BF-n-n Delay setting has expired – indicating that the fault has not
been cleared.
Both 50BF-n-1 and 50BF-n-2 can be mapped to any output contact or LED.
If the 50BF-n CB Faulty input (MENU: INPUT CONFIG\INPUT MATRIX\CB Faulty) is energised when a CB trip
is given the time delays 50BF-n-n Delay will be by-passed and the output given immediately.
Operation of the CB Fail elements can be inhibited from:
Inhibit 50BF-n A binary or virtual input.
Figure 5-1 Logic Diagram: Circuit Breaker Fail Protection (50BF)

Table of Contents

Related product manuals