Instruction manual AQ101, AQ101D, AQ110P, AQ01 12 (48)
2 CONFIGURATION
2.1 DIP SWITCHES (AQ101, AQ101D, AQ110P)
Functionality such as tripping logic is configured using dipswitch settings. Tripping
may be selected based on arc light only or arc light and current thresholds.
Scheme selection is made with dip switches by calculating the sum
of weight factors
2.1.1 AQ101, AQ101D
2.1.1.1 Scheme 0
SW 1
no
Text
Function at ON position
Function at OFF position
8
L> / L> + I>
Tripping with light only criterion.
Tripping with light and current
criterion.
7
S1: L> / L> + I>
Sensor 1 tripping with light only
criterion.
Sensor 1 tripping with light and
current criterion.
6
Latch: On / Off
Output relays latched.
Output relays not latched.
5
100 / 150 ms*
Circuit breaker failure protection
operating time 100 ms.
Circuit breaker failure protection
operating time 150 ms.
4
Scheme
Select
Weight factor 0
Weight factor 8
3
Weight factor 0
Weight factor 4
2
Weight factor 0
Weight factor 2
1
Weight factor 0
Weight factor 1
Table 2-1: AQ101, AQ101D scheme 0 DIP switches definition.
*) Circuit breaker failure protection function is not included in the scheme 0.
8
7
6
5
4
3
2
1
ON
OFF