Chapter 3 Maintenance and Troubleshooting
21
Fault Type 3: -1 Vdc < V
SIG
< 0 Vdc
Possible causes:
Probe is incorrectly gapped (too close to target)
Incorrect power source voltage
Faulty Proximitor Sensor
Probe is detecting other material than target (counterbore or machine case)
Short or open circuit in a connector (dirty or wet) or loose connectors
Short or open circuit in the probe
Short or open circuit in extension cable
Check for fault condition Type 1 on page 14
Is the probe gapped correctly?
Are counterbore dimensions correct?
(see probe installation on page 2)
No
Re-gap the probe
or check
counterbore.
Retest system.
Yes
N
Step 2 Step 1
Original probe/extension
cable
Known good probe with correct length
cable (open gap with probe held away
from conductive material)
V
SIG