Fire & Security Products
Siemens Building Technologies Group 04.2002
3.1 Programming switches, jumpers
Battery type: S2
To set temperature compensation according to information from the various battery
manufacturers.
Possible battery variants Programming switch S2
Var. Battery manufacturer Battery model S2-1 S2-2 S2-3 S2-4
0 off off off off
1 on off off off
2 Varta
Shin-Kobe (Hitachi)
Kobe PSD (Power Storage
Germany)
CF 12-24 (VM 1224)
HP..-12
HP..-12
off on off off
3 Genesis G12V120W15 on on off off
4 Sunrise
Panasonic
LCL 12V24S
LCL 12V..P
off off on off
5 Phoenix (Korea) FNC 12..0 on off on off
6 Yuasa NP..-12B off on on off
7 Sonnenschein Dryfit A212/..G5 on on on off
8 Power-Sonic PS12..0 off off off on
9 Hagen Drysafe HDS-12..0NB on off off on
10 Sonnenschein Dryfit A512/..G5 off on off on
11 ALARMCOM (FIAMM)
1)
FG... on on off on
12 off off on on
13 on off on on
14 off on on on
15 on on on on
”S2” is set to variant 11 (ALARMCOM) at the factory
1)
available from index ’AA’ onwards
Monitoring signals: S3
For settings refer to the „Application examples”, chapter 4
Operating mode: R66, R67
Operating mode: R66 R67
a) Battery operation and symmetry monitoring
b) Battery operation without symmetry monitoring –
c) Operation with external voltage (instead of battery) –
d) Operation without battery or external voltage – –
Door contact simulation: X2
Without door contact: insert jumper X2 at first E3C021.
Factory settings →
without jumper ex factory →