K44 Duo Installation & User manual 19
ENG
Set door held warning time
If the door is still open when the opening time has
expired, a buzzer sounds as to remind the visitor to
close the door immediately – or the alarm output
will be activated. The buzzer sounds until the door
is closed.
Note that door contacts must be connected and that
Door control must be activated for this to work.
This is how to change the door held warning time, if
needed:
Enter A29.
Enter the desired door held warning time (01-99)
with two digits, e.g. 09 for 9 seconds.
Choose to which relay outputs the new door held
warning time should apply:
0 = both
1 = relay output 1
2 = relay output 2
1�
2�
3�