LEDs and connectors
2.2 LEDs
CP 1242-7 GPRS V2
26 Operating Instructions, 10/2016, C79000-G8976-C311-02
DIAG
(red / green)
NETWORK
(red / green)
CONNECT
(green)
SIGNAL
QUALITY
(yellow /
green)
TELE-
SERVICE
(green)
Meaning
flashing
green
- - Telecontrol configuration exists, partner not
reachable, CPU in RUN mode
flashing
green
- - Telecontrol configuration exists, partner not
reachable, CPU in STOP mode
TeleServiceconnection
-
- -
TeleService connection established
- - - -
No TeleService connection established
Quality of the mobile wireless connection
- - -
- Good network (-73 ... -51 dBm)
- - -
- Medium strength network (-89 ... -74 dBm)
- - -
- Weak network (-109 ... -90 dBm)
- - -
- No network (≤ -110 dBm)
flashing red
- -
- Missing external power supply
Loading firmware
Loading firmware.
The "DIAG" LED flashes alternating red and
green.
flashing
green
Firmware was successfully loaded.
flashing red
Error loading firmware
or
Internal error of the CP; remedy: Power
OFF → ON