Configuration and operation
4.11 TeleService
CP 1242-7 GPRS V2
Operating Instructions, 10/2016, C79000-G8976-C311-02
89
An asterisk (*) after a phone number body authorizes connection establishment for all
nodes connected to the body (extension numbers).
Example: +49123456* authorizes +49123456101, +49123456102, +49123456207 etc.
Note
No wake-up without an authorized phone number
If the "Authorized phone numbers" list is empty, the CP cannot be woken up for connection
establishment.
4.11.2
Establishment of a TeleService connection
Requirement for the engineering station and the STEP 7 project
The STEP 7 project with the CP is stored on the engineering station.
The required configuration steps have been performed, see section Configuration of the
TeleService access (Page 87).
Requirement for TeleService via a telecontrol connection: TeleService server
In TeleService via telecontrol, a TeleService server is required as the intermediary between
S7 station and engineering station, see also the section Requirements for operation
(Page 15).
Telecontrol server
If you use a telecontrol server, the intermediary can be the telecontrol server.
TeleService gateway
If there is no telecontrol server in your system, a TeleService gateway must exist as the
intermediary.
For documentation of the two systems, refer to References (Page 129).
Remember the following when establishing TeleService connections via mobile wireless.
Note
TeleService only by a TIA Portal instance
You can operate TeleService with a certain S7 station only from a single engineering station
(TIA Portal instance / STEP 7 project). TeleService using several engineering stations at the
same time with a station is not possible.
TeleService with severa
l engineering stations with different S7 stations is possible if the
suitable STEP 7 project exists on every engineering station.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CP 1242-7 GPRS V2 and is the answer not in the manual?

Siemens CP 1242-7 GPRS V2 Specifications

General IconGeneral
BrandSiemens
ModelCP 1242-7 GPRS V2
CategoryController
LanguageEnglish

Related product manuals