EasyManua.ls Logo

Siemens CP 1243-7 LTE - Configuration Limits and Performance Data

Siemens CP 1243-7 LTE
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application and properties
1.5 Configuration limits and performance data
CP 1243-7 LTE
18 Operating Instructions, 04/2017, C79000-G8976-C381-03
1.5
Configuration limits and performance data
Number of simultaneous connections for telecontrol communication
1 reserved connection for user data exchange with the telecontrol server
Number of simultaneous TeleService connections
Max. 1 TeleService connection
Number of simultaneous connections for S7 communication and Open User Communication
A maximum total of 22 connection resources for S7 communication and Open User
Communication (OUC)Open User Communication (OUC)
The maximum number can be divided up as follows into:
S7 connections: Maximum 8
(PUT/GET)
OUC connections Maximum 8
TCP connections
ISO-on-TCP connections
UDP connections
Additional free resources for S7 or OUC connections: Maximum 6
Number of connections to NTP servers
Max. 1 connection to an NTP server
Number of possible partners for inter-station communication
Max. 13 CPs as partners for inter-station communication
Of which:
Sending
Max. 3 partners
Note: In total along with the telecontrol server it is possible to send to max. 4 partners.
The send buffer would divide itself up proportionately with 4 partners, i.e. 16000 event
messages for each partner.
Receiving
Max. 10 partners
Partners can be S7-1200 CPs with data point configuration and use of the protocol
"TeleControl Basic".