Installation and connecting up 
  3.1 Important notes on using the device 
CP 1542SP-1, CP 1542SP-1 IRC, CP 1543SP-1 
Operating Instructions, 01/2017, C79000-G8976-C426-03 
31 
 
Notes on use in hazardous areas according to ATEX / IECEx 
 
Requirements for the cabinet/enclosure 
To comply with EU Directive 94/9 (ATEX95), the enclosure or cabinet must meet the 
requirements of at least IP54 in compliance with EN 60529. 
 
If the cable or conduit entry point exceeds 70 °C or the branching point of conductors 
exceeds 80 °C, special precautions must be taken. If the equipment is operated in an air 
ambient in excess of 50 °C, only use cables with admitted maximum operating temperature 
of at least 80 °C. 
 
 
Take measures to prevent transient voltage surges of more than 40% of the rated voltage. 
This is the case if you only operate devices with SELV (safety extra-low voltage). 
 
Notes on use in hazardous areas according to UL HazLoc 
 
 
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE 
NON-HAZARDOUS. 
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-
hazardous locations only. 
This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations 
only.