Configuration and operation
4.5 Telecontrol communication (CP 1542SP-1 IRC)
CP 1542SP-1, CP 1542SP-1 IRC, CP 1543SP-1
Operating Instructions, 01/2017, C79000-G8976-C426-03
61
Format (memory
requirements)
Data point type
DNP3 object group
[variations]
Direction
S7 data types
Operand area
Integer (32 bits)
Counter Static
20 [1]
in
UDInt, DWord
I, Q, M, DB
Frozen Counter
2)
21
[1, 5] in
Counter Event
22 [1, 5]
in
UDInt, DWord
I, Q, M, DB
Frozen Counter Event
3)
23 [1, 5]
in
Analog Input
30 [1]
in
DInt
Q, M, DB
Analog Input Event
32 [1]
in
DInt
Q, M, DB
Analog Output Status
4)
40 [1, 3]
out
Analog Output
41 [1]
out
DInt
Q, M, DB
Analog Output Event
4)
42 [1]
out
Floating-point number
(32 bits)
Analog Input
30 [5]
in
Real
Q, M, DB
Analog Input Event
32 [5, 7]
in
Real
Q, M, DB
Analog Output Status
4)
40 [3]
out
Analog Output
41 [3]
out
Real
Q, M, DB
Analog Output Event
4)
42 [5, 7]
out
Floating-point number
(64 bits)
Analog Input
30 [6]
in
LReal
Q, M, DB
Analog Input Event
32 [6, 8]
in
LReal
Q, M, DB
Analog Output
41 [4]
out
LReal
Q, M, DB
Analog Output Event
4)
42 [6, 8]
out
Block of data (1...64
bytes)
5)
Octet String / Octet
String Output
110
[ - ] in, out
5)
DB
Octet String Event
5)
111 [ - ]
in, out
5)
DB
1)
This object group can be configured in the Data point editor of STEP 7 using the substitute object group 12.
2)
This object group can be configured in the Data point editor of STEP 7 using the substitute object group 20.
3)
This object group can be configured in the Data point editor of STEP 7 using the substitute object group 22.
4)
This object group can be configured in the Data point editor of STEP 7 using the substitute object group 41.
5)
With these data point types, contiguous memory areas up to a size of 64 bytes can be transferred. All S7 data types with
a size between 1 and 64 bytes are compatible.
Explanation of the table footnotes
1)
,
2)
,
3)
,
4)
: Configuring data points using substitute object
groups
The initial data point types of the following object groups can be configured using the
substitute object groups listed above:
10 [2]
11 [1, 2]
21 [1, 2, 5, 6]
23 [1, 2, 5, 6]
40 [1, 2, 3]
42 [1, 2, 4, 5, 6, 7, 8]
To configure the DNP3 CP, use the specified substitute object group.