Configuration and operation   
4.5 Telecontrol communication (CP 1542SP-1 IRC) 
  CP 1542SP-1, CP 1542SP-1 IRC, CP 1543SP-1 
68  Operating Instructions, 01/2017, C79000-G8976-C426-03 
Status IDs - TeleControl Basic 
The status bits are converted to the OPC quality code as follows by TCSB. 
●  Quality = BAD, If: 
NON_EXISTENT or OVER_RANGE = 1 
●  Quality = UNCERTAIN, If: 
RESTART or CARRY or SB = 1 
●  Quality = GOOD, If: 
Bits 1, 2, 3, 5 and 6 = 0 
Table 4- 4  Bit assignment of status byte 0 
  -  NON_ 
SB  LOCAL_ 
FORCED 
CARRY  OVER_ 
RANGE 
RESTART  ONLINE 
  -  Data point 
does not 
exist or S7 
address 
unreachable 
Substitute 
value 
(Bit is not 
set)
 
Counted 
value over-
flow before 
reading the 
value 
Limit value 
of the ana-
log value 
prepro-
cessing 
overshot / 
Value not 
yet updated 
after start 
Value is 
valid, CPU 
in RUN 
 
1  1 
(irrelevant)
  1  1  1  1 
Status IDs - TeleControl Basic 
The status IDs can be evaluated by the master. They correspond to the following elements 
of the specification: 
OBJECT FLAGS - DNP3 Specification, Volume 6, Data Object Library - Part 1 
Table 4- 5  Bit assignment of the status byte 
  -  -  -  LOCAL_ 
DISCONTI 
OVER_ 
RESTART  ONLINE 
  -  -  -  Local opera-
tor control 
Counted 
value over-
flow before 
reading the 
value 
Limit value of 
the analog 
value prepro-
cessing over-
shot / 
Value not 
updated after 
start 
Value is 
invalid 
 
(always
1  1  1  1  1