Diagnostics and upkeep
5.1 Loading firmware
CP 342-5 / CP 342-5 FO
40 Manual, 07/2017, C79000-G8976-C146-10
4. Check the configuration of the PG/PC.
Click the "Modify" button to set the access point of the application and the interface
parameter assignment in the "Set PG/PC Interface" diaöog.
The "Set PG/PC interface" dialog opens.
Make the following settings for the access point of the application and the interface
parameter assignment of the PC CP:
CP 342-5 (5DA03): FWL_FAST_LOAD
This profile "FWL_FAST_LOAD" is supported as of SIMATIC STEP 7 V5.5 SP1.
CP 342-5 FO (5DF00): FWL
Confirm the changes with "OK".
5. Check the settings.
Click "Next".
The Firmware Loader opens the dialog "Step 4".
6. Note the specifications of point 1 ... 6 in the dialog for step 4 of the Firmware Loader!
7. If the station is prepared according to the instructions, start loading with the "Download"
button.
You can follow the loading of the firmware file with the LED pattern of the CP, see section
LED displays (Page 29).