EasyManua.ls Logo

Siemens CU240E-2 - Page 14

Siemens CU240E-2
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installing
3.4 Factory setting of the CU240B-2 interfaces
CU240B-2 and CU240E-2 Control Units
14 Compact Operating Instructions, 01/2017, A5E39910322B AA
Control Units with USS interface
The fieldbus interface is not active.
--- No function.
DO 0: p0730
AO 0: p0771[0]
DI x: r0722.x
AI 0: r0755[0]
Speed setpoint (main setpoint): p1070[0] = 755[0]
Figure 3-4 Factory setting of the CU240B-2 Control Unit
Changing the function of the terminals
The function of the terminals marked in color in the two figures above, can be set.
In order that you do not have to successively change terminal for terminal, several terminals
can be jointly set using default settings ("p0015 Macro drive unit").
The terminal settings made in the factory described above correspond to the following
default settings:
Default setting 12 (p0015 = 12): "Standard I/O with analog setpoint"
Default setting 7 (p0015 = 7): "Fieldbus with data set switchover"
Further default settings can be found in the Operating Instructions.
Overview of the manuals (Page 33)

Other manuals for Siemens CU240E-2

Related product manuals