10
Siemens Schweiz AG A6V11646018_en--_k
Smart Infrastructure 2023-02-27
Field device supply (Onboard)
AC 24V output current (terminal V~) Max. 2A, short-circuit proof
1)
DC 24V output current (terminal V+) Max. 100mA, short-circuit proof, protected against
incorrect wiring with AC 24V
1)
Sum of onboard V~ and TXM module V~ currents is max. 2A.
Screw terminals, plug-in
Cu-wire or Cu-strand with wire end sleeve 1 x 0.6mm ∅ to 2.5mm
2
(22 to 14AWG)
or 2 x 0.6mm ∅ to 1.0mm
2
(22 to 18AWG)
Cu-strand without wire end sleeve 1 x 0.6mm ∅ to 2.5mm
2
(22 to 14AWG)
or 2 x 0.6mm ∅ to 1.5mm
2
(22 to 16AWG)
Stripping length 6...7.5mm (0.24...0.29 in)
Screwdriver Slot screws, screwdriver size 1 with shaft ø = 3 mm
Max. tightening torque 0.6 Nm (0.44 lb ft)
On PXC4.E16
Modbus RTU interface
Interface type EIA-485, electrically isolated
Baud rate 300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600, 76800, 115200 (depending on the configuration)
Internal bus termination 120 Ohm, switchable with DIP switch
Internal bus polarization 270 Ohm pull-up/pull-down resistances, switchable with
DIP switch
Cabling (in-house cabling only)
Cable length
3-wire cable, shielded cable recommended (shield must
be connected to building earth in the mounting panel)
Max. 1000 m (3300 ft)
Protection Short-circuit proof
Protection against faulty wiring with AC 24 V