EasyManua.ls Logo

Siemens Desigo PXC4.E16 - Wiring and Connections; Connection Terminals; Field Device Wiring

Siemens Desigo PXC4.E16
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
Siemens Schweiz AG A6V11646018_en--_k
Smart Infrastructure 2023-02-27
Connection terminals
68 69 70
3 4
5 6 7
8 9
Terminal Symbol Description Module Channel
1, 2 2 x RJ45 interface for Ethernet with switch
3, 4 KNX PXC4.E16: KNX PL-Link
5, 6 24 V ~,
Operating voltage AC24V
7 Functional ground (must be connected on the installation side with
the building grounding system (PE)).
9 to 17
20 to 28
Ux Universal inputs / outputs 1…12 61 1…12
Measuring ground for Ux
8, 19 V+ DC 24V power for field devices 2.4W / <100mA
18, 29 V~ AC 24V power for field devices 48VA / 2A
68, 69, 70 COM PXC4.E16: Interface EIA-485 (Modbus RTU)
Term on, off PXC4.E16: Switch for bus termination
Polar on, off Switch for polarization
75 to 86 DOx Relay outputs 1…4 11 1…4
Wiring lines for field devices
Wiring length max. 300 m (1,000ft), CU wire or CU strand.
Cross-section depending on the signal
30m (100ft) applies for signal types AI NTC10K and AI NTC100K
or 300m (984ft) with shielding
Examples of connection diagrams for universal inputs/outputs
Digital inputs
Ux
S1 Feedback contact (NO)
Ux
S2 Feedback contact (NC)
Count inputs: Counter inputs, that count faster than 1 Hz and are laid with more than 10 meters using analog inputs in
the same cable duct, must be shielded.

Related product manuals