Outputs
12 universal inputs / outputs U1...U12 with the following output functions (10-bit DA
converter):
Voltage output, analog
Type Range (over range) Resolution Output current
AO 0-10V 0...10V (-0.05…10.6V) 1mV Max. 1mA
AO 0-10V
standard
0...100%
0% = 0V, 100% = 10V
(-0.05...10.6 V)
0.01% Max. 1mA
Relay output (outputs DO1...DO4)
External supply line fusing
Non-renewable fuse
Circuit breakers
Max. 10 A, slow
Max. 13 A, characteristic B, C, D as per EN60898
Switching voltage AC/DC Max. AC 250 V / DC 30 V
Min. AC/DC 12 V
Current load AC NO contact: Max. 4 A resistive, 3 A inductive (cos phi
0.6)
NC contact: max. 2 A resistive, 1.5 A inductive (cos phi
0.6)
Min. 1 mA at AC 250 V
Min. 10 mA at AC 12 V
Current on make AC NO contact: Max. 10A (1s)
NC contact: Max. 3A (1s)
Current load DC NO contact: Max. 3A resistive at DC 30V
NC contact: Max. 1A resistive at DC 30V
Min. 10 mA resistive at DC 12V
Response / release time 7ms / 3ms typical
Contact life at AC 250 V (reference values)
At 0.3 A resistive
NO contact at 3A resistive
NC contact at 2A resistive
Reduction factor for inductive load (cos phi = 0.6)
5 x 10
5
switching cycles
1 x 10
5
switching cycles
1 x 10
5
switching cycles
0.6
Insulating strength between relay contacts and system
electronics (reinforced insulation).
AC 3750V, as per EN 60730-1