12 / 20
Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02
Building Technologies Workflow with RXT10 and SBT generic plug-in 23 Sep 2011
Step Procedure
6
Configure the gateway:
Select Node Object
SCPTmaxSendTime: Sending interval L
ONWORKS
Recommendation: Same as RXC
Default 2700 [s] (45 min)
UCPTenoceanRcvTm: Receive time
For monitoring the RF link to the room unit
(optional)
UCPTspMax/MinValue: Setpoint Offset ( 3 K, default)