Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02
Building Technologies Workflow with RXT10 and SBT generic plug-in 23 Sep 2011
Step Procedure
7
Configure the gateway:
Select Sensor Object [0...8]
…SCPTmax/minRnge: Measuring range of temperature sensor
[0...40 C, default]
SCPTmaxSendTime: Sending interval L
ONWORKS
Recommendation: Same as RXC
Default 2700 [s] (45min)
8 > Close > Active Plug-in finish
Network > Disconnect (Attached offnet)
9
Make RXT10 bindings:
Datapoint Gateway RXC
Room Temperature: nvoHVACTemp_x nviSpaceTemp
Setpoint Offnet: nvoSetpoint_x nviSetpointOffset
10
Netwok > Connect (online)
11
Assign devices and install
12 Device > Configure > OK