Siemens DOW1171 - Technical Data for Radio Smoke Detector DOW1171

Siemens DOW1171
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
Technical data for radio smoke detector DOW1171
8
76 | 82
Building Technologies
009865_m_en_
--
Fire Safety
2015-11-06
8.2 Technical data for radio smoke detector DOW1171
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
Document 010087
Radio Number of radio detectors per radio gateway Max. 30
Sending/receiving aerials 2 (aerial diversity)
Radio transmission:
Frequency range 868…870 MHz, SRD band (Short Range Device)
Channel grid 25 kHz
Transmitting power <5 mW ERP
Range:
– In building Max. 40 m
– Outdoors Max. 200 m
Battery Number of batteries 2
Voltage DC 9 V
Type:
Block / Li/MnO2
ULTRALIFE U9VL-J or EVE CR9V/P-S
Capacitance 1200 mAh
Service life >5 years
Battery voltage monitored Yes
Ambient conditions Operating temperature -10…+55 °C
Storage temperature -30…+65 °C
Air humidity 95 % rel.
Protection category (IEC 60529) IP44
Mechanical data Dimensions (diameter x H) with base DBW1171 119 x 73 mm
Color ~RAL 9010 pure white
Standards European standards: EN 54-7
EN 54-25