WL Circuit Breaker selection and application guide
39
Ratings for UL1066 Listed non-automatic switches
  WL frame ratings    Frame  size 2        Frame size 3
      800 - 2000A        3200 - 5000A       
 Rating Group    L  F
1
      L  F     
  Breaking capacity with external relay (kA RMS)  254VAC  100  20      100  40   
  50/60 Hz, instantaneous trip  508VAC  100  20      100  40      
    635VAC    85  20        85  40           
  Short-time current Icw (kA RMS)  0.5 sec.    65  20      100  40
1
 Interrupt rating is 200kA based on fuse rating.
2
 Do not apply switch or breaker rated at 635VAC to a system with fault current >85kA RMS.   
 
Low Voltage Power Circuit Breaker
Ratings for UL1066 Listed (ANSI C37) breakers
1
2
2
2
2
2
2
2
2
2
2
2
  WL frame ratings â Frame size 3    3200A      4000A              5000A
  Rating Group    M     F     H  L       M      F       H       L  M       F          
  Interrupting current frame Ics   254VAC 150  150  85 100  150  200 85  100 150 200   
  (kAIR RMS) 50/60 Hz  508VAC  150  150    85  100    150   200  85   100  150  200     
    635VAC    85  100    85    85      85   200  85    85    85  200             
 Short-time current Icw (kA RMS)  0.5 sec.  100  100    85  100    100     40  85  100  100    40     
  Extended instantaneous protection     508VAC  150  150    85  100    150   200  85   100  150  200       
  rating (kA RMS)  635VAC    85  100    85    85      85   200  85     85    85  200      
  Close and latch rating (kA RMS)    100  100    85  100    100     40  85  100   100    40    
  Applicable rating plug range    800 - 3200A      800 - 4000A          800 - 5000 A             
  IEC 60-947-1 impulse withstand rating    8 primary /2.5     8 primary /2.5           8 primary /2.5 
      secondary connection    secondary connection      secondary connection       
  Mechanical make-time (ms)    35      35              35              
  Mechanical break-time (ms)    34      34              24           
  Electric close make-time (ms)    50      50              50         
  Electric trip/ UV break-time (ms)    40/73      40/73              40/73             
  Electric trip and reclose interval (ms)    80      80              80           
  Mechanical duty cycles (no maint.)    10,000      10,000              10,000           
  Electrical duty cycles (no maint)    10,000      10,000              10,000         
  Draw-out breaker efficiency (Watts loss at rated I
n)  700     1100          1650            
  Draw-out fused breaker efficiency (Watts loss at rated I
n)  Consult factory    Consult factory          Consult Factory         
  Ambient operating temperature (ÂșC) w/o LCD     -25 to 70      -25 to 70             -25 to 70