WL Circuit Breaker selection and application guide
Low Voltage Circuit Breaker
Electronic trip units (ETU)
ETU models and features
         
  Features and characteristics  ETU745  ETU748  ETU776     
  Long-time overcurrent protection (L)   X  X  X        
  Short-time delayed overcurrent protection (S)  X  X  X      
  Instantaneous overcurrent protection (I)   X    X     
  Neutral conductor protection (N)  X  X  X      
  Ground fault protection (G)  O  O  O     
  Selectable neutral protection   X  X  X      
  Defeatable short-time protection  X    X        
  Defeatable instantaneous protection  X    X     
  Selectable thermal memory   X  X  X     
  Zone selective interlocking  X  X  X      
 Selectable I
2
t or fixed short-time delay   X  X  X      
  Adjustable instantaneous pick-up   X  X  X     
 Selectable I
2
t  or I
4
t  long-time delay   X  X  X        
  Adjustable short-time delay and pick-up  X  X  X      
  Selectable and adjustable neutral protection  X  X  X    
  Dual protective setting capability      X       
  Dynamic arc-flash sentry (DAS)      X     
  Extended instantaneous protection (EIP)  X  X  X     
  Parameterization by rotary switches  X  X       
  Parameterization by communication (absolute values)       X     
  Parameterization by menu/keypad (absolute values)       X    
  Remote parameterization of the alarm functions      X       
  Remote parameterization of the relay functions      X       
  Alphanumeric display  O  O  X       
  Graphical display      X       
  Power metering function  O  O  O      
  Communication via PROFIBUS-DP  O  O  O        
  Communication via the MODBUS   O  O  O     
  Communication via the Ethernet (BDA)  O  O  O
 (X) = standard feature, (O) = optional feature