Planning
Planning in rooms with inclined ceilings
4
39
Building Technologies
007016_i_en_--
Fire Safety 2012-09-07
4.4.1 Ceilings with uneven inclines
In the case of ceilings with uneven inclines, the detector must be slid sideways to
the flatter roof incline. Define the distance between the detector and the ceiling (2)
using the room height (1).
1
2
Position on ceilings with uneven inclination
1 Room height 2 Distance between detector and
ceiling
Example: In the case of a room height of 10 m, the distance between the detector
and ceiling is 40 to 90 cm.
See also
Distance between detector and ceiling [➙ 43]