Mounting / Installation
5
Electrical connection
56
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
5.3.1 Connection to an addressed detector line
The following applies to FDnet/C-NET detector lines:
Loops, stubs and T-branches are possible.
You may only connect external alarm indicators to one detector.
Permissible cables for detectors with more than one external alarm indicator
according to the collective connection diagram may be migrated to the
FDnet/C-NET without any changes.
Note document 001508 for installation (calculation of the capacity layer).
5.3.1.1 Use of unshielded cables
The connection is established from base to base using twisted or non-twisted wire
pairs.
LINE
+
-
-
+
1
2
3
4
2
+
4
+
LINE
++
__
+
_
LINE
++
__
+
_
LINE
++
__
+
_
LINE
++
__
+
_
LINE
++
__
+
_
Connection diagram for addressed detector line with and without external alarm indicators
(without shielded cables)
1 Control panel 3 Auxiliary terminals DBZ1190-xx
2 Detector 4 External alarm indicator