Commissioning
6
Set parameter set
64
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
6.1 Set parameter set
Setting the parameter set depends on the detector line.
FDnet/C-NET detector line
The parameter set is set using control panel.
The procedure for setting the parameter set via the control panel is described in the
control panel documentation.
Collective detector line
The parameters are set with the DIP switches in the detector unit.
Use DIP switches (1) to set the parameter set you want (see table below).
1
Detector unit with DIP switches
Parameter set DIP switch
No. Name Alarm for n %
attenuation
1 2 3 4 5 6
01 Standard with open line 65 %
ON
OFF
OFF
OFF
OFF
OFF
02 Standard with British
Standard Alarm
65 %
OFF
ON
OFF
OFF
OFF
OFF
03 Sensitive with open line 50 %
ON ON
OFF
OFF
OFF
OFF
04 Sensitive with British
Standard Alarm
50 %
OFF
OFF
ON
OFF
OFF
OFF
05 Very sensitive with open
line
30 %
ON
OFF
ON
OFF
OFF
OFF
06 Very sensitive with British
Standard Alarm
30 %
OFF
ON
ON
OFF
OFF
OFF
Set parameter set
See also
Determine parameter set [➙ 51]