Commissioning
Commissioning the adjustment device
6
69
Building Technologies
007016_i_en_--
Fire Safety 2012-09-07
Indication on the adjustment device
The indication before the initialization differs from that after initialization. The
indication is described in the table below.
Indication location Example Meaning
555 Signal level before initialization
Must be between 255 and 1195 for
initialization. Otherwise initialization is not
possible.
Top left
100% Standardized signal value as % of the
current compensation value
During initialization, the signal level is
equalized to the compensation value 100 %.
Bottom left 50m Distance in meters between detector and
reflector
Top right Adjust Detector not yet initialized
Bottom right OK Last initialization successfully completed
Indication before initialization:
555
djust
50m
Indication after initialization:
100%
50m
OK