Commissioning
Checking the signal level and distance
6
71
Building Technologies
007016_i_en_--
Fire Safety 2012-09-07
Possible reasons for the signal level and distance indication deviating:
The detector and the reflector are not positioned on the same horizontal or
vertical axis.
The detector is not mounted on an even surface.
3
4
5
6
7
8
9
3
2
1
Checking the signal level and distance
1 Horizontal scale 6 Connection sockets
2 Knurled screw for horizontal
adjustment
7 Vertical scale
3 Safety screws 8 Knurled screw for vertical
adjustment
4 Button 9 Opening for cable entry
5 Adjustment device
Example: Signal level and distance indication in the 'Adjust' menu:
555
A
djust
50m
See also
Preliminary setting of the detector optics (optional) [➙ 72]
Fine-tuning of the detector optics [➙ 73]