Communication blocks
2-36 Function Blocks - FM 458-1 DP
Edition 12.2004
2.4.3 CBRFAW Receiving warnings from a COMBOARD
CBRFAW
EXM448 module name, connector
GV CTS CW W
COMBOARD alarms 96 - 81
QTS BO
Module status
YTS W
Status, COMBOARD alarm
channel
• The block can only be configured on a FM458 module.
• This block receives warnings A81 to A96 of a COMBOARD
(communications submodule of SIMOVERT MASTER DRIVES, e.g.
CBP2 for PROFIBUS DP).
• Input CTS of the CBRFAW function block is used to define from which
COMBOARD the warnings are to be received.
• Function block CBRFAW may only be configured on a FM458 module
of each COMBOARD. It is configured on the FM458 module, on which
a @FMPAR function block was also configured for the appropriate
COMBOARD.
Initialization inputs:
CTS Configured name of the EXM448/EXM448-2 module and connector X01 or X02, separated by
".".
(Default: - )
Outputs:
CW Outputs COMBOARD warnings A81 to A96
(Default: 0)
QTS Block status:
• QTS=1: Block is being processed and is operating error-free.
• QTS=0: Block is shut down due to a fault with error output at YTS.
(Default: 0)
YTS Status of the COMBOARD warning channel:
YTS=0: OK condition
For additional values, refer to: D7-SYS online help "Help on events". (press the F1 key in the
CFC and call-up the topic "Help on events" under "CFC for SIMADYN D".)
(Default: 0)
Symbol
Brief description
I/O