SIMOLINK drive coupling
5-16 Function Blocks - FM 458-1 DP
Edition 12.2004
TAD
Hardware address SLB (name of the SLB module), which can be
configured in HWConfig
FSL
Address of the first slave to which setpoint XO0 should be set, value
range 1 . . . 200
(initialization connection)
(default: 1)
NSL
Number of slaves to which the setpoint should be sent, value range
1. . . 8
(initialization connection)
(default: 1)
ACL
Axis cycle length
Upper integrator limit value
(default: 0)
CTV
Channel number for setpoint 2, value range 0 . . . 7
(initialization connection)
(default: 0)
CSV
Number of the channel on which the setpoint is sent,
Value range 0 . . . 7
(initialization connection)
(default: 0)
XSA
Common setpoint XS of the main angle/position for all NSL slaves (default: 0)
XO0
to
XO7
Setpoint offset XO for slaves 1 to 8,
A maximum of 8 setpoint offsets can be sent.
(default: 0)
SEQ
Sequence number
Number of the block in the SIMOLINK block sequence
This value provides information as to whether the block was correctly
initialized.
(default: 0)
YF
Error status of the block
YF=0 no error, YF > 0 refer to coded error output @SL
(default: 0)
QF
Group error bit
QF=0 no error, QF=1 for error (if YF0)
(default: 0)
Computation time [µs] FM 458-1 DP 39,6
Can be inserted online No
Can be configured in Interrupt tasks
Cyclic tasks
Executed in Initialization mode
Normal mode
Special features -