8
Building Technologies 009197_h_--_--
Fire Safety 2016-04-20
Weight FC2030 12,2 kg
FC2060 17 kg
FC2020 7,3 kg
FC2040 11,6 kg
FT2040 4,7 kg
Operating voltage FP2001 (70W) AC 115…230 V, 50 / 60 Hz
FP2015 (70W) AC 115 V / 230 V, 50 / 60 Hz
SV 24V-150W AC 115 V / 230 V, 50 / 60 Hz
Protection category according
to IEC 60529
IP30
Altitude FP2001 (70W) Max. 4000 m above sea level
FP2015 (70W) Max. 4000 m above sea level
SV 24V-150W Rev. A1-A4 Max. 2000 m above sea level
SV 24V-150W Rev. A5 Max. 3900 m above sea level
Ambient conditions Operating temperature -8…+42 °C
Storage temperature -25…+60 °C
Air humidity 95 % rel.