Operation (short) MP 2.1
FC20xx Fire control panel
FT2040 Fire terminal
ALARM-Procedure Page 1
Switching off detector zones / detectors Page 2
Switching on detector zones / detectors Page 4
Procedure in case of Fault Page 4
Document ID: 009906_d_en_GB
Edition: 05.2009
1 of 4
ALARM Procedure
with Alarm Verification Concept (AVC), suggested possible procedure, subject to local requirements
Action / Condition Consequence / Status
1.
Press <Acknowledge> on the PMI before allowed
response time (t1) runs out (Password required)
Buzzer is turned off, alarm is acknowledged.
Countdown t2 for the investigation of the cause of alarm starts.
2.
Read top line on display:
"Fire brigade in" "mm:ss"
Remaining time is shown as countdown before building
evacuation and Fire Brigade call.
3.
Read fire location on display.
4.
Go to the fire location.
Information on the cause of ALARM,
damage limitation.
5.
Decide: MAJOR INCIDENT or minor incident.
If required, initiation of suitable emergency measures.
6.
MAJOR INCIDENT:
A
Press <Alarm delay off>
or actuate nearest manual call point.
Read top line on display:
"Remote transmission activated"
"Fire brigade called !"
"Call fire brigade !"
Remote transmission switched off / not available or
defective.
The remote transmission for fire alarm is activated
immediately.
Transmission to fire brigade not confirmed yet.
ALARM transmitted to fire brigade.
Fire brigade must be called by phone!
No automatic transmission to fire brigade.
Dial the following no.:
Minor incident:
R
Press <Reset>.
(Password required)
Fire detection system is in normal condition unless another event
occurs.
It may be necessary to vent the room before resetting is possible.
Elements that cannot be reset can be switched off temporarily.
7.
During the alarm, optionally press
<Sounders Evacuate> on the PMI.
(Password required)
Deactivates the acoustic alarm devices during the alarm.
(Reactivation is possible by pressing the button again)
1 2 3
4 5 6
7 8 9
*
0 #
C
ok
a
b
c
~
g
h
i
j
k
l
m
n
o
p
q
r
s
t
u
v
w
x
y
z
d
e
f
ALARM
FAUL
T
ISOLATION
DETECTOR TES
T
System
On
Fault
Scroll alarms
Remote alarm
Active
Fault / Off
Sounders
Fault / Off
Active Evacuate
Silence buzzer
Acknowledge
Reset
Alarm delay off
Premises manned
Fire brigade in
001 ALARM
Autom. FIRE ALARM Zone no.2
Execute
Commands
More
Options
Fx20x
x
Control function
Fault / Of
Active
7.
A
2.
1.
R
6.
5
.
4.
Go to fire location
Decide
00:02:51
Switch to
Standard view
3.
Main Building
Ground Floor
1/01 Meeting Room 001
00:02:51

Other manuals for Siemens FT2040

Question and Answer IconNeed help?

Do you have a question about the Siemens FT2040 and is the answer not in the manual?

Siemens FT2040 Specifications

General IconGeneral
TypeFire Alarm Control Panel
Protection RatingIP30
NetworkableYes
Operating Voltage230V AC
Relative HumidityUp to 95% non-condensing

Summary

ALARM Procedure

Key Steps in Alarm Response

Details on acknowledging the alarm, verifying location, and deciding on incident type.

Switching off detector zones detectors

Procedure to Switch Off Detector Zones

Step-by-step guide to isolate detector zones from the main menu via Functions.

Switching off a detector

Procedure to Switch Off a Single Detector

Guide for isolating individual detectors through the Topology and Detection tree menus.

Switching on detector zones detectors

Procedure to Switch On Detector Zones

Guide to re-enable detector zones using the Message Summary and Isolations menu.

Procedure in case of Fault

Fault Handling Steps

Steps to silence, acknowledge, and rectify faults on the fire control panel.

Related product manuals