Siemens GH180 - Controlled Outgoing Circuit for Auxiliary Equipment 230 V 1 AC or 120 V 1 AC (Option N37); Controlled Outgoing Circuit for Auxiliary Equipment 230 V 1 AC or 120 V 1 AC (Option N38); Table 3-13 Outgoing Circuit for Auxiliary Equipment (Option N33); Table 3-14 T-X30 Terminal Strip for Connecting Auxiliary Equipment

Siemens GH180
224 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.1.6.39 Controlled outgoing circuit for auxiliary equipment 230 V 1 AC or 120 V 1 AC (option N37)
This option provides a controlled output that is protected via the motor circuit breaker and is
used for operating external auxiliary equipment (e.g. separately-driven fan for motor, pumps,
and oil supplies).
The contactor is energized by means of an ON command on the converter. The OFF command
deactivates the contactor.
Table 3-13 Outgoing circuit for auxiliary equipment (option N33)
Controlled outgoing circuit for auxiliary equipment Setting range of the motor circuit breaker
120 V 1 AC, 60 Hz, max. 2.1 KW
230 V 1 AC, 50 Hz, max. 3.5 KW
Table 3-14 T-X30 terminal strip for connecting auxiliary equipment
Supplying the auxiliary voltage Outgoing circuit for auxiliary equip‐
ment
Feedback: auxiliary equipment ON
Terminal Connector Terminal Connector Terminal Connector
.T–X30:6 U1 .T–X30:3 U1 .T–X30:1 Relay contact
max. 60 V DC
.T–X30:7 V1 .T–X30:4 V1 .T–X30:2
.T–X30:8 W1 .T–X30:5 W1
Note
The infeed required for the drive power supply must be provided externally.
3.1.6.40 Controlled outgoing circuit for auxiliary equipment 230 V 1 AC or 120 V 1 AC (option N38)
This option provides a controlled output that is protected via the motor circuit breaker and is
used for operating external auxiliary equipment (e.g. separately-driven fan for motor, pumps,
and oil supplies).
The contactor is energized by means of an ON command on the converter. The OFF command
deactivates the contactor.
Table 3-15 Outgoing circuit for auxiliary equipment (option N33)
Controlled outgoing circuit for auxiliary equipment Setting range of the motor circuit breaker
120 V 1 AC, 60 Hz, max. 2.8 KW
230 V 1 AC, 50 Hz, max. 4.5 KW
Description
3.1 Cabinet Details
SINAMICS PERFECT HARMONY GH180 6SR41 manufactured in NMA Nuernberg, Germany