ISGS Settings Worksheet for Date: Set A
S-6 Siemens Energy & Automation, Inc.
A2400
Phase Sequence Voltage (47)
Negative Sequence Voltage (47N)
A2401 Function 47 Enabled Disabled
2410 Freeze Waveform 1 47 --- on Trip None
2411 Freeze Waveform 2 47 --- on Trip None
A2451 Function 47N Enabled Disabled
A2452 Curve 47N Inverse Definite Inverse
A2453 Pickup 47N 10% Range: 4-40% (1% steps) %
A2454 Time Delay 47N(Defin.) 0.00 s
Range: 0-100 s (0.01 s steps),
or
s
A2455 Time Dial 47N (Inverse) 0.10 Range: 0.1-9.9 (0.1 steps)
A2456 Maximum Time (Inverse) 120 s Range: 1-250 s (1 s steps) s
A2457 Block 47N by 40 V Range: 40-120 V (1 V steps) V
2460 Freeze Waveform 1 47N on pickup on Trip None
2461 Freeze Waveform 2 47N on pickup on Trip None