ISGS Settings Worksheet for Date: Set A
Siemens Energy & Automation, Inc. S-9
3400 Value Supervision
3401 Voltage Balance Function Enabled Disabled
3402 Voltage Balance Pickup 100 V Range: 40-120 V (0.1 V steps) V
3404 Voltage Balance Factor 0.80
Range: 0.58-0.95
(0.01 teps)
3411 Current Sum Function Enabled Disabled
3412 Current Sum Pickup 5 A CT 0.5 A Range: 0.5-5 A (0.1 A steps) A
1 A CT 0.1 A Range: 0.1-1 A (0.1 A steps) A
3414 Current Sum Factor 0.10
Range: 0.10-0.95
(0.01 steps)
3411 Current Balance Function Enabled Disabled
3412 Current Balance Pickup 5 A CT 2.5 A Range: 0.5-5 A (0.1 A steps) A
1 A CT 0.1 A Range: 0.1-1 A (0.1 A steps) A
3414 Current Balance Factor 0.80
Range: 0.10-0.95
(0.01 steps)
3500 Breaker Operation
3501 Interrupted Current Function Enabled Disabled
3502 Interrupted Current Pickup 1000.00 kA
Range: 0-9999.9 kA
(1 kA steps)
kA
3503 Breaker Operations Functions Enabled Disabled
3504 Breaker Operations Counter 100 Range: 0-65535
S
isv3o_1.bk : isv3o_cf.frm Page 9 Wednesday, August 7, 1996 10:51 AM