EasyManua.ls Logo

Siemens KNX EIB TP-UART 2-IC - Page 23

Siemens KNX EIB TP-UART 2-IC
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GAMMA instabus
Release: February 2012
KNX EIB TP-UART 2-IC
Siemens AG pages 42 Technical Manual
Infrastructure and Cities Sector,
Building Technologies
Control Products and Systems © Siemens AG 2012 page 23
P. O. Box 10 09 53, Subject to change without further notice.
D-93009 Regensburg
3.2.3.1.6 U_ResetBusyMode
The service U_ResetBusyMode deactivates immediately the BUSY mode in the TP-UART. All
addressed telegrams are answered according to the intern address flags. The host shall synchronize
its receiver before sending the U_ResetBusyMode.
UART-Controlfield (22
hex
)
7 6 5 4 3 2 1 0
0 0 0 1 0 0 1 0
Fig. 9: U_ResetBusyMode
3.2.3.1.7 U_SetAddress
This service configures the physical address of the TP-UART. If this service is repeatedly sent (e.g. the
physical address changes), the new address will be active in the TP-UART after reception of the
complete U_SetAddress service and when no Layer 2 frame is currently received from the EIB. If the
address is set a complete address evaluation in the TP-UART is activated (group-addressed telegrams
are now generally confirmed).
Note: The TP-UART does not evaluate the received EIB telegrams which were sent itself.
After reset the address evaluation is deactivated again.
UART-Controlfield (28
hex
)
7 6 5 4 3 2 1 0
0 0 1 0 1 0 0 0
physical address high physical address low
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
a a a a l l l l d d d d d d d d
Fig. 10: U_SetAddress
The TP-UART analyzes after setting the physical address independently of the host controller all
telegrams and evaluates the destination address. If addressed then the IACK generation takes place.
The TP-UART analyses for this reasons the different frame formats (standard frame and extended
frame format according to the KNX standard).
- Frameformat Standard:
Octet 0 ... Octet 3 Octet 4 Octet 5 ...
Ctrlbyte
10R1cc00
... High byte
destaddress
Low byte
destaddress
NPCI
Axxx xxxx
...