Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
131/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
Postpurge-
PosAux1
Postpurge position of auxiliary damper (gas) 0..90°
0..100 %
Service 25° x x
Postpurge-
PosAux2
Postpurge position of auxiliary damper 2 0..90° Service 25° x
Postpurge-
PosAux3
Postpurge position of auxiliary damper 3 0..90° Service 25° x
Postpurge-
PosVSD
Postpurge position of VSD 0..100 % Service 50 % x
ProgramStop Program stop deactivated
24 PrePurgP
32 PreP FGR
36 IgnitPos
44 Interv 1
52 Interv 2
72 PostPPos
76 PostPFGR
Service deactivated x x
ResetIgnitPos Resetting the ignition positions to invalid value Service x x
IgnitionPosGas Service x x
IgnitionPosAir Service x x
IgnitionPosAux1 Service x x
IgnitionPosAux2 Service x
IgnitionPosAux3 Service x
IgnitionPosVSD Service x
CurveParams Service x x
LoadLimits Setting the minimum and maximum load limits Service x x
MinLoadGas Minimum load "Low fire" (gas) 0..MaxLoadGas Service 0 % x x
MaxLoadGas Maximum load "High fire" (gas) MinLoadGas..100 % Service 100 % x x
AuxActuator Auxiliary actuator for firing on gas: Deactivate / activate / VSD
operation
deactivated
Damper act
VSD activat
OEM deactivated x
AirActuator Air actuator for firing on gas: Deactivate / activate / air-
regulating
deactivated
activated
air influen
OEM air influen x
AuxActuator 1 Auxiliary actuator 1 for firing on gas: Deactivate / activate / air-
regulating
deactivated
activated
air influen
OEM air influen x