Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
132/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
AuxActuator 2 Auxiliary actuator 2 for firing on gas: Deactivate / activate / air-
regulating
deactivated
activated
air influen
OEM deactivated x
AuxActuator 3 Auxiliary actuator 3 for firing on gas: Deactivate / activate / air-
regulating
deactivated
activated
air influen
OEM deactivated x
VSD VSD for firing on gas: Deactivate / activate / air-regulating deactivated
activated
air influen
OEM air influen x
OilSettings Parameter settings for firing on oil Service x x
SpecialPosi-
tions
Setting the special actuator positions for firing on oil Service x x
HomePos Setting the home positions for firing on oil Service x x
HomePosOil Home position of fuel damper (oil) 0..90° Service x x
HomePosAir Home position of air damper (oil) 0..90° Service x x
HomePosAux1 Home position of auxiliary damper (oil) 0..9
0..100 %
Service x x
HomePosAux2 Home position of auxiliary damper 2 0..90° Service x
HomePosAux3 Home position of auxiliary damper 3 0..90° Service x
HomePosVSD Home position of VSD 0..100 % Service x
PrepurgePos Setting the prepurge positions for firing on oil Service x x
PrepurgePosAir Prepurge position of air damper (oil) 0..90° Service 90° x x
Prepurge-
PosAux1
Prepurge position of auxiliary damper (oil) 0..90°
0..100 %
Service 90° x x
Prepurge-
PosAux2
Prepurge position of auxiliary damper 2 0..90° Service 90° x
Prepurge-
PosAux3
Prepurge position of auxiliary damper 3 0..90° Service 90° x
Prepurge-
PosVSD
Prepurge position of VSD 0..100 % Service 100 % x
IgnitionPos Setting the ignition positions for firing on oil Service x x
IgnitionPosOil Ignition position of fuel damper (oil) 0..90° Service invalid x x
IgnitionPosAir Ignition position of air damper (oil) 0..90° Service invalid x x
IgnitionPosAux1 Ignition position of auxiliary damper (gas) 0..90°
0..100 %
Service invalid x x
IgnitionPosAux2 Ignition position of auxiliary damper 2 0..90° Service invalid x