Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
133/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
IgnitionPosAux3 Ignition position of auxiliary damper 3 0..90° Service invalid x
IgnitionPosVSD Ignition position of VSD 10..100 % Service invalid x
PostpurgePos Setting the postpurge positions for firing on oil Service x x
PostpurgePosOil Postpurge position of fuel damper (oil) 0..90° Service 0° x x
PostpurgePosAir Postpurge position of air damper (oil) 0..90° Service 15° x x
Postpurge-
PosAux1
Postpurge position of auxiliary damper (oil) 0..90°
0..100 %
Service 25° x x
Postpurge-
PosAux2
Postpurge position of auxiliary damper 2 0..90° Service 25° x
Postpurge-
PosAux3
Postpurge position of auxiliary damper 3 0..90° Service 25° x
Postpurge-
PosVSD
Postpurge position of VSD 0..100 % Service 50 % x
ProgramStop Program stop deactivated
24 PrePurgP
32 PreP FGR
36 IgnitPos
44 Interv 1
52 Interv 2
72 PostPPos
76 PostPFGR
Service deactivated x x
ResetIgnitPos Resetting the ignition positions to invalid value Service x x
IgnitionPosOil Service x x
IgnitionPosAir Service x x
IgnitionPosAux1 Service x x
IgnitionPosAux2 Service x
IgnitionPosAux3 Service x
IgnitionPosVSD Service x
CurveParams Setting the curve parameters of ratio control for firing on oil Service x x
Curve Settings Service x x
Operation Mode Selection of burner operating mode (multistage or modulating)
for oil
Two-stage
Three-stage
Modulating
OEM Modulating x x
LoadLimits Setting the minimum and maximum load limits Service x x
MinLoadOil Minimum load "Low fire" (oil) 0..MaxLoadOil Service 0 % x x
MaxLoadOil Maximum load "High fire" (oil) MinLoadOil..100 % Service 100 % x x