Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
134/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
AuxActuator Auxiliary actuator for firing on oil: Deactivate / activate / VSD
operation
deactivated
Damper act
VSD activat
OEM deactivated x
AirActuator Air actuator for firing on oil: Deactivate / activate / air-regulating deactivated
activated
air influen
OEM air influen x
AuxActuator 1 Auxiliary actuator 1 for firing on oil: Deactivate / activate / air-
regulating
deactivated
activated
air influen
OEM air influen x
AuxActuator 2 Auxiliary actuator 2 for firing on oil: Deactivate / activate / air-
regulating
deactivated
activated
air influen
OEM deactivated x
AuxActuator 3 Auxiliary actuator 3 for firing on oil: Deactivate / activate / air-
regulating
deactivated
activated
air influen
OEM deactivated x
VSD VSD for firing on oil: Deactivate / activate / air-regulating deactivated
activated
air influen
OEM air influen x
Autom/Manual/O
ff
Selection of manual or automatic operation Automatic
Burner on
Burner off
User Automatic x x
Times Service x x
OperatRampMod Duration operating ramp ratio control modulating operation 30..120 s Service 30 s x x
OperatRamp-
Stage
Duration operating ramp ratio control multistage operation 10..60 s Service 10 s x x
TimeNoFlame Duration ramp in prepurge and ignition position 10..120 s Service 10 s x x
NumFuelActua-
tors
Number of fuel actuators 1..2 OEM 2 x x
ShutdownBehav This parameter determines the way the ratio control system
behaves in the lockout phase
Unchanged
PostpurgeP
HomePos
Service HomePos x x
ProgramStop Program stop deactivated
24 PrePurgP
32 PreP FGR
36 IgnitPos
44 Interv 1
Service deactivated x x